Installation and Start-up
Copyright
2001 Phone: (614) 771-2718 RE-ACM
Vanner Inc. FAX: 614-771-4904 Owners/Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 0.1a
Hilliard Ohio 43026 RE-ACM-Owners_Man_R01a.doc
18
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
The Output Neutral is
Not Bonded
to Ground internally.
All of the ACM’s electrical connections are labeled.
Place ALL Disconnects on the ACM and Service Disconnects in the OFF position to avoid electrical
shock.
Remove the access covers to the DC and AC raceways.
F 7 Figure 5.2-2 ACM AC Raceway Connections
INVERTER
IN
INVERTER
OUT
UTILITY
IN
GENERATOR
IN
L1
N
L2
GND
L1
N
L2
GND
L1
N
L2
GND
L1
N
L2
GND
BACK
FRONT
RIGHT
LEFT
F 8 Figure 5.2-3 RE-ACM to RE-4500 AC Interconnections
L1
L1L2
N
Bottom
Left
N
L2
GND
UTILITYLOAD
GND
Bottom
L1
L1
L2
N
N
L2
GND
INV ININV OUT
GND
L1
L1
L2
N
N
L2
GND
GENERATORUTILITY
GND
Right
RE24-4500DGT
RE24-ACM
From
Generator
From
Utility
Generator Connection:
Connect 240 Volt Vrms Three wire Generator L1, L2, N, and GND to the AC
Generator terminals using 12 gauge wire minimum (10 gauge recommended for best performance).
Verify that the AC Generator cables are still disconnected from the AC Generator. Insert AC Generator
cables through the entry/exit port and into the AC wiring raceway. Connect L1, N, L2 and ground to the
appropriate terminals in the terminal strip and torque each of the AC terminal screws to 15 inch pounds.
Re-torque after 30 days.
Utility Connection:
Connect 240 Volt Vrms Three wire Utility L1, L2, N, and GND to the AC Utility
terminals using 12 gauge wire minimum (10 gauge recommended for best performance).